[{"data":1,"prerenderedAt":972},["ShallowReactive",2],{"blog-post-nl-30ma-aardlek-per-stopcontact":3,"blog-alternates-30ma-rcd-per-socket":235},{"id":4,"title":5,"articleId":6,"body":7,"category":206,"date":207,"description":208,"extension":209,"lastUpdated":210,"locale":211,"meta":212,"navigation":213,"path":214,"publishDate":207,"readTime":215,"refreshInterval":216,"seo":217,"slug":218,"stem":219,"tags":220,"__hash__":234},"blog\u002Fblog\u002F30ma-rcd-per-socket.nl.md","Heb ik een 30mA differentieel nodig per stopcontact?","30ma-rcd-per-socket",{"type":8,"value":9,"toc":195},"minimark",[10,15,28,32,35,84,89,135,139,142,158,161,170,174,189],[11,12,14],"h2",{"id":13},"nee-maar-elke-stopcontactkring-heeft-er-wel-een-nodig","Nee — maar elke stopcontactkring heeft er wel een nodig",[16,17,18,19,23,24,27],"p",{},"Een veelvoorkomend misverstand: u hebt ",[20,21,22],"strong",{},"niet"," voor elk afzonderlijk stopcontact een aparte 30mA differentieel nodig. De AREI-vereiste heeft betrekking op ",[20,25,26],{},"stroomkringen",", niet op individuele aansluitpunten. Eén 30mA differentieelschakelaar beschermt doorgaans meerdere stopcontacten die op dezelfde stroomkring zijn aangesloten.",[11,29,31],{"id":30},"wat-zegt-het-arei","Wat zegt het AREI?",[16,33,34],{},"Het AREI (Algemeen Reglement op de Elektrische Installaties) bepaalt in meerdere artikelen wanneer een 30mA differentieelbescherming verplicht is:",[36,37,38,51],"table",{},[39,40,41],"thead",{},[42,43,44,48],"tr",{},[45,46,47],"th",{},"Artikel",[45,49,50],{},"Vereiste",[52,53,54,65,74],"tbody",{},[42,55,56,62],{},[57,58,59],"td",{},[20,60,61],{},"Art. 4.2.4.3_b",[57,63,64],{},"Stopcontactkringen (evenals verlichting, bad\u002Fdouche, wasmachines\u002Fdroogkasten\u002Fvaatwassers) moeten beschermd zijn door een 30mA differentieel",[42,66,67,71],{},[57,68,69],{},[20,70,61],{},[57,72,73],{},"Maximaal 8 vertrekkende kringen per 30mA differentieel (geldt niet voor de 300mA-bescherming aan het voedingspunt)",[42,75,76,81],{},[57,77,78],{},[20,79,80],{},"Art. 7.1.4.3",[57,82,83],{},"In de badkamer is 30mA-bescherming altijd verplicht (Hoofdstuk 7.1 voor ruimtes met bad\u002Fdouche)",[85,86,88],"h3",{"id":87},"belangrijkste-limieten","Belangrijkste limieten",[36,90,91,101],{},[39,92,93],{},[42,94,95,98],{},[45,96,97],{},"Criterium",[45,99,100],{},"Limiet",[52,102,103,111,119,127],{},[42,104,105,108],{},[57,106,107],{},"Max. kringen per 30mA differentieel",[57,109,110],{},"8",[42,112,113,116],{},[57,114,115],{},"Max. stopcontacten per kring",[57,117,118],{},"8 (verplicht volgens Art. 5.3.5.2_b)",[42,120,121,124],{},[57,122,123],{},"Nominale stroom stopcontactkring",[57,125,126],{},"16A of 20A",[42,128,129,132],{},[57,130,131],{},"Min. kabeldoorsnede stopcontacten",[57,133,134],{},"min. 2,5 mm² (ongeacht 16 A of 20 A beveiliging; voor verlichting volstaat 1,5 mm² bij 16 A)",[11,136,138],{"id":137},"praktijkvoorbeeld","Praktijkvoorbeeld",[16,140,141],{},"Een typische eengezinswoning heeft bijvoorbeeld 6 stopcontactkringen. Deze kunnen over twee 30mA differentieelschakelaars worden verdeeld:",[143,144,145,152],"ul",{},[146,147,148,151],"li",{},[20,149,150],{},"Diff 1"," (30mA, Type A): stopcontacten woonkamer, gang, slaapkamer 1 — 3 kringen",[146,153,154,157],{},[20,155,156],{},"Diff 2"," (30mA, Type A): stopcontacten keuken, slaapkamer 2, bureau — 3 kringen",[16,159,160],{},"Zo valt niet het hele huis zonder stroom als één differentieel uitschakelt, en u blijft onder de limiet van 8 kringen per differentieel.",[162,163,164],"blockquote",{},[16,165,166,169],{},[20,167,168],{},"Let op",": Voor badkamers (Art. 7.1.4.3) schrijft het AREI bijzondere beschermingsmaatregelen voor. In huishoudelijke installaties (Art. 4.2.4.3_b) moeten de kringen van ruimtes met bad en\u002Fof douche beschermd zijn door een differentieelstroombeveiliging met hoge gevoeligheid (30 mA).",[11,171,173],{"id":172},"gerelateerde-artikelen","Gerelateerde artikelen",[143,175,176,183],{},[146,177,178],{},[179,180,182],"a",{"href":181},"\u002Fblog\u002Feendraadschema-maken","Eendraadschema zelf maken — stap voor stap",[146,184,185],{},[179,186,188],{"href":187},"\u002Fblog\u002Felektrische-keuring","Elektrische keuring in België — wat u moet weten",[16,190,191],{},[179,192,194],{"href":193},"\u002F","Maak nu uw AREI-conform eendraadschema — gratis →",{"title":196,"searchDepth":197,"depth":197,"links":198},"",2,[199,200,204,205],{"id":13,"depth":197,"text":14},{"id":30,"depth":197,"text":31,"children":201},[202],{"id":87,"depth":203,"text":88},3,{"id":137,"depth":197,"text":138},{"id":172,"depth":197,"text":173},"faq","2026-03-04","Nee — maar per stroomkring wel. Ontdek wat het AREI voorschrijft en wanneer een 30mA differentieelschakelaar verplicht is.","md","2026-06-05","nl",{},true,"\u002Fblog\u002F30ma-rcd-per-socket.nl","3 min",12,{"title":5,"description":208},"30ma-aardlek-per-stopcontact","blog\u002F30ma-rcd-per-socket.nl",[221,222,223,224,225,226,227,228,229,230,231,232,233],"AREI","RGIE","differentieel","differentieelschakelaar","30mA","aardlekschakelaar","stopcontact","stroomkring","elektrische keuring","elektrische installatie","België","eendraadschema","situatieschema","VkD5rBnhiP5FybfLKJdAiTCWJF4V4Vvl745ZXFnIcqw",[236,435,643,834],{"id":237,"title":238,"articleId":6,"body":239,"category":206,"date":207,"description":415,"extension":209,"lastUpdated":210,"locale":416,"meta":417,"navigation":213,"path":418,"publishDate":207,"readTime":215,"refreshInterval":216,"seo":419,"slug":420,"stem":421,"tags":422,"__hash__":434},"blog\u002Fblog\u002F30ma-rcd-per-socket.de.md","Brauche ich einen 30mA FI-Schalter für jede Steckdose?",{"type":8,"value":240,"toc":407},[241,245,256,260,263,303,307,352,356,359,373,376,384,388,402],[11,242,244],{"id":243},"nein-aber-jeder-steckdosen-stromkreis-braucht-einen","Nein — aber jeder Steckdosen-Stromkreis braucht einen",[16,246,247,248,251,252,255],{},"Ein häufiges Missverständnis: Man braucht ",[20,249,250],{},"nicht"," für jede einzelne Steckdose einen eigenen FI-Schutzschalter (Differentieel). Die AREI-Vorschrift bezieht sich auf ",[20,253,254],{},"Stromkreise",", nicht auf einzelne Anschlusspunkte. Ein 30mA-FI-Schutzschalter schützt in der Regel mehrere Steckdosen, die am selben Stromkreis angeschlossen sind.",[11,257,259],{"id":258},"was-sagt-das-arei","Was sagt das AREI?",[16,261,262],{},"Das AREI (Allgemeine Reglementierung der Elektrischen Installationen) legt in mehreren Artikeln fest, wann ein 30mA-Differentialschutz Pflicht ist:",[36,264,265,274],{},[39,266,267],{},[42,268,269,271],{},[45,270,47],{},[45,272,273],{},"Vorschrift",[52,275,276,285,294],{},[42,277,278,282],{},[57,279,280],{},[20,281,61],{},[57,283,284],{},"Steckdosenstromkreise (sowie Beleuchtung, Bad\u002FDusche, Wasch-\u002FTrockner\u002FSpülmaschinen) müssen über einen 30mA-FI geschützt sein",[42,286,287,291],{},[57,288,289],{},[20,290,61],{},[57,292,293],{},"Maximal 8 Endstromkreise pro 30mA-FI (gilt nicht für den 300mA-Schutz am Speisepunkt)",[42,295,296,300],{},[57,297,298],{},[20,299,80],{},[57,301,302],{},"Im Badezimmer ist 30mA-Schutz immer Pflicht (Kapitel 7.1 für Räumlichkeiten mit Badewanne\u002FDusche)",[85,304,306],{"id":305},"grenzwerte-im-überblick","Grenzwerte im Überblick",[36,308,309,319],{},[39,310,311],{},[42,312,313,316],{},[45,314,315],{},"Kriterium",[45,317,318],{},"Grenzwert",[52,320,321,328,336,344],{},[42,322,323,326],{},[57,324,325],{},"Max. Stromkreise pro 30mA-FI",[57,327,110],{},[42,329,330,333],{},[57,331,332],{},"Max. Steckdosen pro Stromkreis",[57,334,335],{},"8 (Pflicht gemäß Art. 5.3.5.2_b)",[42,337,338,341],{},[57,339,340],{},"Nennstrom Steckdosen-Stromkreis",[57,342,343],{},"16A oder 20A",[42,345,346,349],{},[57,347,348],{},"Kabelquerschnitt Steckdosen",[57,350,351],{},"min. 2,5 mm² (unabhängig ob 16 A oder 20 A Absicherung; für Beleuchtung reicht 1,5 mm² bei 16 A)",[11,353,355],{"id":354},"praxisbeispiel","Praxisbeispiel",[16,357,358],{},"Ein typisches Einfamilienhaus hat z.B. 6 Steckdosen-Stromkreise. Diese können auf zwei 30mA-FI-Schutzschalter aufgeteilt werden:",[143,360,361,367],{},[146,362,363,366],{},[20,364,365],{},"FI 1"," (30mA, Typ A): Steckdosen Wohnzimmer, Flur, Schlafzimmer 1 — 3 Stromkreise",[146,368,369,372],{},[20,370,371],{},"FI 2"," (30mA, Typ A): Steckdosen Küche, Schlafzimmer 2, Büro — 3 Stromkreise",[16,374,375],{},"So bleibt bei einer Auslösung nicht das ganze Haus stromlos, und Sie bleiben unter dem Limit von 8 Stromkreisen pro FI.",[162,377,378],{},[16,379,380,383],{},[20,381,382],{},"Achtung",": Für Badezimmer (Art. 7.1.4.3) schreibt das AREI besondere Schutzmaßnahmen vor. In hauswirtschaftlichen Anlagen (Art. 4.2.4.3_b) müssen die Stromkreise von Räumlichkeiten mit Badewanne und\u002Foder Dusche über eine Differenzstrom-Schutzeinrichtung mit hoher Empfindlichkeit (30 mA) geschützt sein.",[11,385,387],{"id":386},"verwandte-artikel","Verwandte Artikel",[143,389,390,396],{},[146,391,392],{},[179,393,395],{"href":394},"\u002Fde\u002Fblog\u002Feindrahtschema-erstellen","Eindrahtschema selbst erstellen — Schritt für Schritt",[146,397,398],{},[179,399,401],{"href":400},"\u002Fde\u002Fblog\u002Felektrische-abnahme","Elektrische Abnahme in Belgien — was Sie wissen müssen",[16,403,404],{},[179,405,406],{"href":193},"Erstellen Sie jetzt Ihr AREI-konformes Eindrahtschema — kostenlos →",{"title":196,"searchDepth":197,"depth":197,"links":408},[409,410,413,414],{"id":243,"depth":197,"text":244},{"id":258,"depth":197,"text":259,"children":411},[412],{"id":305,"depth":203,"text":306},{"id":354,"depth":197,"text":355},{"id":386,"depth":197,"text":387},"Nein — aber pro Stromkreis. Erfahren Sie, was das AREI vorschreibt und wann ein 30mA FI-Schutzschalter Pflicht ist.","de",{},"\u002Fblog\u002F30ma-rcd-per-socket.de",{"title":238,"description":415},"30ma-fi-pro-steckdose","blog\u002F30ma-rcd-per-socket.de",[221,222,423,424,425,225,426,427,428,429,430,431,432,433],"FI-Schutzschalter","Fehlerstromschutzschalter","Differentialschutz","Steckdose","Stromkreis","Stromabnahme","Keuring","elektrische Installation","Belgien","Eindrahtschema","Situationsplan","33X97574XeTR_70A8ZOq0k41QLDjcD1v3D3luW02pEo",{"id":436,"title":437,"articleId":6,"body":438,"category":206,"date":207,"description":623,"extension":209,"lastUpdated":210,"locale":624,"meta":625,"navigation":213,"path":626,"publishDate":207,"readTime":215,"refreshInterval":216,"seo":627,"slug":6,"stem":628,"tags":629,"__hash__":642},"blog\u002Fblog\u002F30ma-rcd-per-socket.en.md","Do I Need a 30mA RCD for Every Socket?",{"type":8,"value":439,"toc":615},[440,444,463,467,470,511,515,560,564,567,581,584,592,596,610],[11,441,443],{"id":442},"no-but-every-socket-circuit-needs-one","No — but every socket circuit needs one",[16,445,446,447,450,451,455,456,458,459,462],{},"A common misconception: you do ",[20,448,449],{},"not"," need a dedicated 30mA RCD (residual-current device, or ",[452,453,454],"em",{},"différentiel"," \u002F ",[452,457,224],{},") for each individual socket. The AREI\u002FRGIE requirement applies to ",[20,460,461],{},"circuits",", not individual connection points. A single 30mA RCD typically protects multiple sockets connected to the same circuit.",[11,464,466],{"id":465},"what-does-the-arei-say","What does the AREI say?",[16,468,469],{},"The AREI (General Regulations on Electrical Installations) specifies in several articles when 30mA differential protection is mandatory:",[36,471,472,482],{},[39,473,474],{},[42,475,476,479],{},[45,477,478],{},"Article",[45,480,481],{},"Requirement",[52,483,484,493,502],{},[42,485,486,490],{},[57,487,488],{},[20,489,61],{},[57,491,492],{},"Socket circuits (as well as lighting, bath\u002Fshower, washing machines\u002Fdryers\u002Fdishwashers) must be protected by a 30mA RCD",[42,494,495,499],{},[57,496,497],{},[20,498,61],{},[57,500,501],{},"Maximum 8 final circuits per 30mA RCD (does not apply to the 300mA protection at the supply point)",[42,503,504,508],{},[57,505,506],{},[20,507,80],{},[57,509,510],{},"In bathrooms (rooms with bathtub\u002Fshower), 30mA protection is always mandatory (Chapter 7.1)",[85,512,514],{"id":513},"key-limits-at-a-glance","Key limits at a glance",[36,516,517,527],{},[39,518,519],{},[42,520,521,524],{},[45,522,523],{},"Criterion",[45,525,526],{},"Limit",[52,528,529,536,544,552],{},[42,530,531,534],{},[57,532,533],{},"Max. circuits per 30mA RCD",[57,535,110],{},[42,537,538,541],{},[57,539,540],{},"Max. sockets per circuit",[57,542,543],{},"8 (mandatory per Art. 5.3.5.2_b)",[42,545,546,549],{},[57,547,548],{},"Rated current for socket circuits",[57,550,551],{},"16A or 20A",[42,553,554,557],{},[57,555,556],{},"Min. cable cross-section at 16A",[57,558,559],{},"2.5 mm²",[11,561,563],{"id":562},"practical-example","Practical example",[16,565,566],{},"A typical single-family home might have 6 socket circuits. These can be split across two 30mA RCDs:",[143,568,569,575],{},[146,570,571,574],{},[20,572,573],{},"RCD 1"," (30mA, Type A): Living room, hallway, bedroom 1 sockets — 3 circuits",[146,576,577,580],{},[20,578,579],{},"RCD 2"," (30mA, Type A): Kitchen, bedroom 2, office sockets — 3 circuits",[16,582,583],{},"This way, if one RCD trips, the entire house doesn't lose power, and you stay within the 8-circuit limit per RCD.",[162,585,586],{},[16,587,588,591],{},[20,589,590],{},"Warning",": For bathrooms (Art. 7.1.4.3), the AREI prescribes special protective measures. In residential installations (Art. 4.2.4.3_b), circuits in rooms with a bathtub and\u002For shower must be protected by a high-sensitivity residual-current device (30 mA).",[11,593,595],{"id":594},"related-articles","Related articles",[143,597,598,604],{},[146,599,600],{},[179,601,603],{"href":602},"\u002Fen\u002Fblog\u002Fsingle-line-diagram","How to create a single-line diagram — step by step",[146,605,606],{},[179,607,609],{"href":608},"\u002Fen\u002Fblog\u002Felectrical-inspection","Electrical inspection in Belgium — what you need to know",[16,611,612],{},[179,613,614],{"href":193},"Create your AREI-compliant single-line diagram now — free →",{"title":196,"searchDepth":197,"depth":197,"links":616},[617,618,621,622],{"id":442,"depth":197,"text":443},{"id":465,"depth":197,"text":466,"children":619},[620],{"id":513,"depth":203,"text":514},{"id":562,"depth":197,"text":563},{"id":594,"depth":197,"text":595},"No — but you need one per circuit. Learn what the AREI\u002FRGIE requires and when a 30mA residual-current device is mandatory.","en",{},"\u002Fblog\u002F30ma-rcd-per-socket.en",{"title":437,"description":623},"blog\u002F30ma-rcd-per-socket.en",[221,222,630,631,632,225,633,634,635,636,637,638,639,232,432,640,641],"RCD","residual current device","differential switch","socket","circuit","electrical inspection","keuring","electrical installation","Belgium","single-line diagram","schéma unifilaire","situation plan","gJC3FutzDHcYuZhUuXfdksyvSTvUQNFj8DgfYCys9Hg",{"id":644,"title":645,"articleId":6,"body":646,"category":206,"date":207,"description":819,"extension":209,"lastUpdated":210,"locale":820,"meta":821,"navigation":213,"path":822,"publishDate":207,"readTime":215,"refreshInterval":216,"seo":823,"slug":824,"stem":825,"tags":826,"__hash__":833},"blog\u002Fblog\u002F30ma-rcd-per-socket.fr.md","Ai-je besoin d'un différentiel 30mA par prise ?",{"type":8,"value":647,"toc":811},[648,652,662,666,669,709,713,758,762,765,777,780,788,792,806],[11,649,651],{"id":650},"non-mais-chaque-circuit-de-prises-en-a-besoin","Non — mais chaque circuit de prises en a besoin",[16,653,654,655,658,659,661],{},"Une idée reçue courante : il n'est ",[20,656,657],{},"pas"," nécessaire d'installer un différentiel 30mA dédié pour chaque prise individuelle. L'exigence du RGIE porte sur les ",[20,660,461],{},", pas sur les points de connexion individuels. Un seul différentiel 30mA protège généralement plusieurs prises raccordées au même circuit.",[11,663,665],{"id":664},"que-dit-le-rgie","Que dit le RGIE ?",[16,667,668],{},"Le RGIE (Règlement Général sur les Installations Électriques) précise dans plusieurs articles quand une protection différentielle 30mA est obligatoire :",[36,670,671,680],{},[39,672,673],{},[42,674,675,677],{},[45,676,478],{},[45,678,679],{},"Exigence",[52,681,682,691,700],{},[42,683,684,688],{},[57,685,686],{},[20,687,61],{},[57,689,690],{},"Les circuits de prises (ainsi que l'éclairage, salle de bain\u002Fdouche, lave-linge\u002Fsèche-linge\u002Flave-vaisselle) doivent être protégés par un différentiel 30mA",[42,692,693,697],{},[57,694,695],{},[20,696,61],{},[57,698,699],{},"Maximum 8 circuits départ par différentiel 30mA (ne s'applique pas à la protection 300mA au point d'alimentation)",[42,701,702,706],{},[57,703,704],{},[20,705,80],{},[57,707,708],{},"Dans la salle de bain, la protection 30mA est toujours obligatoire (Chapitre 7.1 pour les locaux avec baignoire\u002Fdouche)",[85,710,712],{"id":711},"limites-essentielles","Limites essentielles",[36,714,715,725],{},[39,716,717],{},[42,718,719,722],{},[45,720,721],{},"Critère",[45,723,724],{},"Limite",[52,726,727,734,742,750],{},[42,728,729,732],{},[57,730,731],{},"Max. circuits par différentiel 30mA",[57,733,110],{},[42,735,736,739],{},[57,737,738],{},"Max. prises par circuit",[57,740,741],{},"8 (obligatoire selon Art. 5.3.5.2_b)",[42,743,744,747],{},[57,745,746],{},"Courant nominal circuit prises",[57,748,749],{},"16A ou 20A",[42,751,752,755],{},[57,753,754],{},"Section min. du câble prises",[57,756,757],{},"min. 2,5 mm² (indépendamment de la protection 16 A ou 20 A ; pour l'éclairage 1,5 mm² suffit à 16 A)",[11,759,761],{"id":760},"exemple-pratique","Exemple pratique",[16,763,764],{},"Une maison unifamiliale typique possède par exemple 6 circuits de prises. Ceux-ci peuvent être répartis sur deux différentiels 30mA :",[143,766,767,772],{},[146,768,769,771],{},[20,770,150],{}," (30mA, Type A) : prises salon, couloir, chambre 1 — 3 circuits",[146,773,774,776],{},[20,775,156],{}," (30mA, Type A) : prises cuisine, chambre 2, bureau — 3 circuits",[16,778,779],{},"Ainsi, si un différentiel se déclenche, toute la maison ne perd pas le courant, et vous restez sous la limite de 8 circuits par différentiel.",[162,781,782],{},[16,783,784,787],{},[20,785,786],{},"Attention"," : Pour les salles de bain (Art. 7.1.4.3), le RGIE prescrit des mesures de protection particulières. Dans les installations domestiques (Art. 4.2.4.3_b), les circuits des locaux avec baignoire et\u002Fou douche doivent être protégés par un dispositif de protection à courant différentiel résiduel à haute sensibilité (30 mA).",[11,789,791],{"id":790},"articles-connexes","Articles connexes",[143,793,794,800],{},[146,795,796],{},[179,797,799],{"href":798},"\u002Ffr\u002Fblog\u002Fschema-unifilaire","Créer un schéma unifilaire — étape par étape",[146,801,802],{},[179,803,805],{"href":804},"\u002Ffr\u002Fblog\u002Fcontrole-electrique","Contrôle électrique en Belgique — ce qu'il faut savoir",[16,807,808],{},[179,809,810],{"href":193},"Créez votre schéma unifilaire conforme RGIE — gratuit →",{"title":196,"searchDepth":197,"depth":197,"links":812},[813,814,817,818],{"id":650,"depth":197,"text":651},{"id":664,"depth":197,"text":665,"children":815},[816],{"id":711,"depth":203,"text":712},{"id":760,"depth":197,"text":761},{"id":790,"depth":197,"text":791},"Non — mais par circuit. Découvrez ce que le RGIE exige et quand un différentiel 30mA est obligatoire.","fr",{},"\u002Fblog\u002F30ma-rcd-per-socket.fr",{"title":645,"description":819},"30ma-ddr-par-prise","blog\u002F30ma-rcd-per-socket.fr",[221,222,454,827,225,828,634,829,830,831,640,232,832],"disjoncteur différentiel","prise","contrôle électrique","installation électrique","Belgique","plan de situation","e1CShyMiP8BtwT3565CygFmYxzxu0f-FzfKTN4cM3qQ",{"id":4,"title":5,"articleId":6,"body":835,"category":206,"date":207,"description":208,"extension":209,"lastUpdated":210,"locale":211,"meta":969,"navigation":213,"path":214,"publishDate":207,"readTime":215,"refreshInterval":216,"seo":970,"slug":218,"stem":219,"tags":971,"__hash__":234},{"type":8,"value":836,"toc":961},[837,839,845,847,849,885,887,923,925,927,937,939,945,947,957],[11,838,14],{"id":13},[16,840,18,841,23,843,27],{},[20,842,22],{},[20,844,26],{},[11,846,31],{"id":30},[16,848,34],{},[36,850,851,859],{},[39,852,853],{},[42,854,855,857],{},[45,856,47],{},[45,858,50],{},[52,860,861,869,877],{},[42,862,863,867],{},[57,864,865],{},[20,866,61],{},[57,868,64],{},[42,870,871,875],{},[57,872,873],{},[20,874,61],{},[57,876,73],{},[42,878,879,883],{},[57,880,881],{},[20,882,80],{},[57,884,83],{},[85,886,88],{"id":87},[36,888,889,897],{},[39,890,891],{},[42,892,893,895],{},[45,894,97],{},[45,896,100],{},[52,898,899,905,911,917],{},[42,900,901,903],{},[57,902,107],{},[57,904,110],{},[42,906,907,909],{},[57,908,115],{},[57,910,118],{},[42,912,913,915],{},[57,914,123],{},[57,916,126],{},[42,918,919,921],{},[57,920,131],{},[57,922,134],{},[11,924,138],{"id":137},[16,926,141],{},[143,928,929,933],{},[146,930,931,151],{},[20,932,150],{},[146,934,935,157],{},[20,936,156],{},[16,938,160],{},[162,940,941],{},[16,942,943,169],{},[20,944,168],{},[11,946,173],{"id":172},[143,948,949,953],{},[146,950,951],{},[179,952,182],{"href":181},[146,954,955],{},[179,956,188],{"href":187},[16,958,959],{},[179,960,194],{"href":193},{"title":196,"searchDepth":197,"depth":197,"links":962},[963,964,967,968],{"id":13,"depth":197,"text":14},{"id":30,"depth":197,"text":31,"children":965},[966],{"id":87,"depth":203,"text":88},{"id":137,"depth":197,"text":138},{"id":172,"depth":197,"text":173},{},{"title":5,"description":208},[221,222,223,224,225,226,227,228,229,230,231,232,233],1787555252781]